Building Construction Fire Resistance Tester, BFR-125, BFR-225, ISO 834, KS F 2275-1, KS F2268-1, KS F2846, KS B6951
Introduction
FESTEC's Building Construction Fire Resistance Tester measures the performance of construction material against standard fire conditions, and satisfies the general requirements, vertical history section material, vertical non-history section material and the fire-proof door's fire proof testing. This equipment tests about the walls, doors, dampers, connections, through type sealing material, etc. such as the product of test for fire resistance.
Standard
-
ISO 834 : Fire-resistance tests -Elements of building construction
Part 1 - General requirements
Part 4 - Specific requirements for load bearing vertical separating elements
Part 5 - Specific requirements for load bearing horizontal separating elements
Part 6 - Specific requirements for beams
Part 7 - Specific requirements for columns
Part 9 - Specific requirements for non-load bearing ceiling elements
-
KS F 2275-1 Methods of fire resistance test for elements of building construction-General requirements
-
KS F 2268-1 Fire resistance test for door assemblies
-
Other Standards : BS 476(20-23), BS EN 1363(1-2), BS EN 1364(1), BS EN 1365(1), BS EN 1366(1-3), BS EN 1634-1, ASTM E 119, ASTM E 814, UL 10(B-C), UL 263, UL 1709, UL 1479, UL 2079, ISO 3008, ISO 3009
Features
-
Vertical/Horizontal/Small Testing Furnace
- Testing main body and Refractories
; Inside dimension : 4,000(W) x 3,000(H) x 1,100(D)mm
- Pattern & PID Control System
- HMI & Control System
- Additional facilities
; Testing specimen frame (Land, Ship, Boring Testing 1 ea)
; Hydraulic Unit & Cylinder
; Testing specimen frame stock and work table
* Excluding testing furnace frontal work Lifter
-
Combustion blocking testing device (Option Parts)
Casing & Frame
Moving & Sealing Unit
; Hydraulic Unit & Cylinder ; LM Guide Rail ; Sealing Gasket
- Additional devices and piping
; Air Supply Fan
; Flow rate and attachment device
- Operating Panel
-
Exhaustion gas discharge device (Option Parts)
- I.D FAN
- Exhaustion Duct
- Exhaustion Amount Control Damper
; Strength and Stack material : Carbon Steel
; Excluding gas collection hood at the upper part of front of the testing furnace
Specification
Model |
FT-BFR-125, FT-BFR-225, FT-BFR-325 |
Size |
3,890(W) x 1,970(D) x 4,940(H)mm(Vertical)
4,925(W) x 3,700(D) x 4,162(H)mm(Blocking Smoking)
6,230(W) x 1,755(D) x 7,095(H)mm(Dust Collector) |
Power |
AC 380V 3-phase, 50/60Hz, 500A |
Weight |
Approx. 7,500kg(Vertical Tester),
Approx. 3,500kg(Blocking Smoking),
Approx. 5,700kg(Dust Collector) |
Manual |
Supply |
Exhaust |
Minimum 800m3/min |
Utilities |
Gas, Hydraulic systems, Water, Personal Computer |
Test Result
-
After applying a certain amount of head within the fireproof door (ISO Curve) and measure the degree of twist (disposition) and any damages due to heat, and additionally measure any flow of heat towards the exterior.
-
During test time, it distribute pressure measurement(Pa) and print for graph
-
During test time, it distribute temperature measurement(oC) and print for graph
-
During test time, record characteristic of specimen and damage